Logo image
Large area impingement spray cooling from multiple normal and inclined spray nozzles
Journal article   Peer reviewed

Large area impingement spray cooling from multiple normal and inclined spray nozzles

Z. B. Yan, F. Duan, T. N. Wong, K. C. Toh, K. F. Choo, P. K. Chan, Y. S. Chua, L. W. Lee and Tsu Wei Kenny Choo
Heat and mass transfer, Vol.49(7), pp.985-990
01/07/2013

Abstract

Mechanics Physical Sciences Science & Technology Technology Thermodynamics
An inclined spray chamber with four multiple nozzles to cool a 1 kW 6U electronic test card has been designed and tested in this study. The multiple inclined sprays can cover the same heated surface area as that with the multiple normal sprays but halve the volume of the spray chamber. The spray cooling system used R134a as a working fluid in a modified refrigeration cycle. It is observed that increasing mass flow rate and pressure drop across the nozzles improved the heat transfer coefficient with a maximum enhancement of 117 %, and reduced the maximum temperature difference at the heated surface from 13.8 to 8.4 A degrees C in the inclined spray chamber with a heat flux of 5.25 W/cm(2), while the heat transfer coefficient of the normal spray increased with a maximum enhancement of 215 % and the maximum temperature difference decreased from 10.8 to 5.4 A degrees C under similar operating conditions. We conclude that the multiple inclined sprays could produce a higher heat transfer coefficient but with an increase in non-uniformity of the surface temperature compared with the multiple normal sprays.

Metrics

1 Record Views

Details

Logo image